MELSEC iQ-F FX5UC CPU Module

Hardware Manual

This manual describes the part names, dimensions, installation, cabling and specifications for the product. This manual is extracted from MELSEC iQ-F FX5UC User's Manual (Hardware). Refer to MELSEC iQ-F FX5UC User's Manual (Hardware) for more details. Before use, read this manual and manuals of relevant products fully to acquire proficiency in the handling and operating the product. Make sure to learn all the product information, safety information, and precautions. And, store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward it to the end user.

Registration: Ethernet is a trademark of Xerox Corporation. MODBUS is a registered trademark of Schneider Electric SA. The company name and the product name to be described in this manual are the registered trademarks or trademarks of each company.

Effective January 2019 Specifications are subject to change without notice.

2015 MITSUBISHI ELECTRIC CORPORATION

Safety Precautions (Read these precautions before use.) If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. This manual classifies the safety precautions into two categories:

and .

Depending on the circ*mstances, procedures indicated by may also cause severe injury. It is important to follow all precautions for personal safety.

Manual Number JY997D61001

Revision G

Date January 2019

Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.

Indicates that incorrect handling may cause hazardous conditions, resulting in minor or moderate injury or property damage.

STARTUP AND MAINTENANCE PRECAUTIONS

Do not touch any terminal while the PLC's power is on. Doing so may cause electric shock or malfunctions.

Before cleaning or retightening terminals, cut off all phases of the power supply externally. Failure to do so in the power ON status may cause electric shock.

Before modifying the program in operation, forcible output, running or stopping the PLC, read through this manual carefully, and ensure complete safety. An operation error may damage the machinery or cause accidents.

Do not change the program in the PLC from two or more peripheral equipment devices at the same time. (i.e. from an engineering tool and a GOT) Doing so may cause destruction or malfunction of the PLC program.

Use the battery for memory backup in conformance to the MELSEC iQ-F FX5UC User's Manual (Hardware). - Use the battery for the specified purpose only. - Connect the battery correctly. - Do not charge, disassemble, heat, put in fire, short-circuit, connect

reversely, weld, swallow or burn the battery, or apply excessive forces (vibration, impact, drop, etc.) to the battery.

Page 4

Associated manuals

Associated manuals FX5UC CPU module comes with this document (hardware manual). For a detailed explanation of the FX5UC CPU module hardware and information on instructions for PLC programming and intelligent function module, refer to the relevant documents.

STARTUP AND MAINTENANCE PRECAUTIONS

- Do not store or use the battery at high temperatures or expose to direct sunlight.

- Do not expose to water, bring near fire or touch liquid leakage or other contents directly.

- When replacing the battery, make sure to use our specified product (FX3U-32BL).

- When a battery error occurs ("BAT" LED is lit in red), follow the description in MELSEC iQ-F FX5UC User's Manual (Hardware).

Incorrect handling of the battery may cause heat excessive generation, bursting, ignition, liquid leakage or deformation, and lead to injury, fire or failures and malfunction of facilities and other equipment.

STARTUP AND MAINTENANCE PRECAUTIONS

Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions. For repair, contact your local Mitsubishi Electric representative.

Turn off the power to the PLC before connecting or disconnecting any extension cable. Failure to do so may cause equipment failures or malfunctions.

Turn off the power to the PLC before attaching or detaching the following devices. Failure to do so may cause equipment failures or malfunctions. - Peripheral devices, expansion adapter, and connector conversion adapter - Extension modules, bus conversion module, connector conversion

module, and battery Do not use the chemicals for cleaning. If there is the possibility of touching the PLC inside a control panel in

maintenance, make sure to discharge to avoid the influence of static electricity. Since there are risks such as burn injuries, please do not touch the

surface of the equipment with bare hands when it is operating in an environment which exceeds ambient temperature of 50C.

DISPOSAL PRECAUTIONS

Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device.

When disposing of batteries, separate them from other waste according to local regulations. (For details on the Battery Directive in EU countries, refer to the MELSEC iQ-F FX5UC User's Manual (Hardware).)

TRANSPORTATION PRECAUTIONS

When transporting the PLC with the optional battery, turn on the PLC before shipment, confirm that the battery mode is set using a parameter and the BAT LED is OFF, and check the battery life. If the PLC is transported with the BAT LED ON or the battery exhausted, the battery-backed data may be unstable during transportation.

The PLC is a precision instrument. During transportation, avoid impacts larger than those specified in the general specifications (Section 2.1) by using dedicated packaging boxes and shock-absorbing palettes. Failure to do so may cause failures in the PLC. After transportation, verify operation of the PLC and check for damage of the mounting part, etc.

When transporting lithium batteries, follow required transportation regulations. (For details on the regulated products, refer to the MELSEC iQ-F FX5UC User's Manual (Hardware).)

How to obtain manuals

For the necessary product manuals or documents, consult with your local Mitsubishi Electric representative.

Manual name Manual No. Description

MELSEC iQ-F FX5 User's Manual (Startup)

JY997D58201

Explains performance specifications, procedures before operation, and troubleshooting of the FX5 CPU module.

MELSEC iQ-F FX5UC User's Manual (Hardware)

JY997D61401 Explains FX5UC CPU module specification details for I/O, wiring, installation, and maintenance.

Page 6

Certification of UL, cUL standards

Please consult with Mitsubishi Electric for information on UL, cUL standard practices and the corresponding types of equipment.

Compliance with EC directive (CE Marking)

This product complies with EC directive, however, this document does not guarantee that a mechanical system including this product will comply with EC directive. Compliance to EMC directive and LVD directive of the entire mechanical system should be checked by the user/manufacturer. For more details please contact the local Mitsubishi Electric sales site.

Caution for compliance with EC Directive Please use the FX5UC CPU modules while installed in conductive shielded

control panels under a general industrialenvironment. Programmable controllers are open-type devices that must be installed and

used within conductive control panels. Please secure the control box lid to the control box (for conduction). Installation within a control box greatly affects the safety of the system and aids in shielding noise from the programmable controller.

For the control panel, use the product having sufficient strength, fire protectiveness and shielding property to an installation environment.

24 V DC of the power supply must be supplied from the circuit double/ reinforced insulated from the main power supply (MAINS).

[Caution for compliance with the LVD directive (EN61010-2-201:2013)]*1

To an external connection port other than AC power supply terminal and AC input/output terminal, connect the circuit separated from a dangerous voltage by a double/reinforced insulation.

Do not wire two or more crimp terminals to one terminal. (If the wiring with two or more wires is needed, take an appropriate action such as adding an external terminal.)

For crimp terminals to be used for the wiring applied with 30 V AC or higher, use the products with insulating sleeves.

Cutoff device such as a breaker or a circuit protector should be installed in accordance with the following precautions. - Use EN60947-1 or EN60947-3 standards. - Place the cutoff device so that it can be operated easily. - Specify that the cutoff device is for this equipment.

*1 For the time of compliance with the LVD directive (EN61010-2-201:2013), refer to MELSEC iQ-F FX5UC User's Manual (Hardware).

Incorporated Items

Check if the following product and items are included in the package:

MELSEC iQ-F FX5 User's Manual (Serial Communication)

JY997D55901

Explains the N:N network, MELSEC Communication protocol, inverter communication and non-protocol communication.

MELSEC iQ-F FX5 User's Manual (MODBUS Communication)

JY997D56101 Explains the MODBUS serial communication.

MELSEC iQ-F FX5 User's Manual (Ethernet Communication)

JY997D56201 Functions for communication via built-in Ethernet port.

Included Items

CPU module

FX5UC-MT/D (: 32, 64, 96)

Product 1 module

FX2NC-100MPCB [1 m, three wire] 1 cable

FX2NC-100BPCB [1 m, two wire] 1 cable

Manuals [Japanese/English] 1 manual

Manuals [Chinese] 1 manual

FX5UC-MT/DSS FX5UC-32MT/DS-TS FX5UC-32MT/DSS-TS FX5UC-32MR/DS-TS (: 32, 64, 96)

Product 1 module

FX2NC-100MPCB [1 m, three wire] 1 cable

Manuals [Japanese/English] 1 manual

Manuals [Chinese] 1 manual

Manual name Manual No. Description

Page 8

1. Outline

1.1 Part names

I/O module

FX5-CEX/D FX5-C32ET/D (: 16, 32)

Product 1 module

FX2NC-10BPCB1 [0.1 m, double- ended]

1 cable

FX5-CEX/DS FX5-C32EX/DS-TS FX5-C32ET/DSS FX5-C32ET/DS(S)-TS FX5-CEYT/D(SS) FX5-C32EYT/D(SS)-TS FX5-C16EYR/D-TS (: 16, 32)

Product 1 module

No. Name

[1] Expansion adapter connecting hooks

[2] Built-in RS-485 communication terminal block

[3] Built-in Ethernet communication connector (with cover)

[4]

Operation status display LEDs

PWR Green On while the PLC is powered.

ERR*1 Red Lit/flashing when an error occurs.

P.RUN Green On while the PLC is running.

BAT Red Lit when the battery voltage drops.

CARD Green Lit when the SD memory card is inserted.

SD/RD Green Lit when data is sent or received through communication via built-in Ethernet.

RD Green Lit when data is received through communication via built-in RS-485.

SD Green Lit when data is sent through communication via built-in RS-485.

Included Items

[5]

[9][10] [18]

[19] [23]

[6]

[20]

[21]

[22]

[6]

[7]

[8] [2]

[3] [17]

[15] [16]

[4]

[1]

[1]

[26]

[24]

[25]

[11]

[14]

Front panel (Spring clamp terminal block type)

Under sideFront panel (Connector type)

With cover open

Left side Right side

[12]

[13]

Page 10

Side B

Side A

Side

B JAPANESE ENGLISH

JY997D61001G

Page 31

*1 When powered on in the factory default state, ERR LED starts flashing because there is no program. For details, refer to the following manual.

MELSEC iQ-F FX5UC Users Manual (Hardware). *2 Products that do not have the genuine product certification label or

nameplate are not covered by the warranty.

1.2 External dimensions and weight

Outer paint color Body: Munsell 0.6B7.6/0.2

[5] Input connector

[6] Extension module connection hooks

[7] Input/Output display LEDs (Green)

[8] DISP switch (for switching Input/Output display LEDs)

[9] Output connector

[10] DIN rail mounting hooks

[11] Input terminal

[12] Input display LEDs (Green)

[13] Output display LEDs (Green)

[14] Output terminal

[15] Terminal names

shows a function grounding terminal.

[16] Power connector for CPU module

[17] RS-485 terminal resister selector switch

[18] Battery cover

[19] Expansion adapter connector cover

[20] Extension connector cover

[21] DIN rail mounting groove

[22] Nameplate printing*2

is a mark that instructs to use the cable with an appropriate temperature rating (80C or more) for wiring.

[23] Genuine product certification label*2

[24] SD memory card disable switch

[25] SD memory card slot

[26] RUN/STOP/RESET switch

Model name W: mm MASS (Weight): kg

FX5UC-32MT/D FX5UC-32MT/DSS

42.1 Approx. 0.2

FX5UC-32MT/DS-TS FX5UC-32MT/DSS-TS

48.1 Approx. 0.25

FX5UC-32MR/DS-TS 68.2 Approx. 0.35

FX5UC-64MT/D FX5UC-64MT/DSS

62.2 Approx. 0.3

FX5UC-96MT/D FX5UC-96MT/DSS 82.3 Approx. 0.35

No. Name 90

W 89.1 74

Unit: mm Connector type

Spring clamp terminal block type

93.7 74

Page 33

2. Installation (general specifications)

As for installation of the I/O modules and expansion adapters, refer to MELSEC iQ-F FX5UC User's Manual (Hardware).

2.1 Generic specifications

INSTALLATION PRECAUTIONS

Use the product within the generic environment specifications described in section 2.1 of this manual. Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S, SO2 or NO2), flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind. If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.

INSTALLATION PRECAUTIONS

Do not touch the conductive parts of the product directly. Doing so may cause device failures or malfunctions.

When drilling screw holes or wiring, make sure that cutting and wiring debris do not enter the ventilation slits of the PLC. Failure to do so may cause fire, equipment failures or malfunctions.

Install the product on a flat surface. If the mounting surface is rough, undue force wi l l be appl ied to the PC board, thereby causing nonconformities.

Install the product securely using a DIN rail or mounting screws. Connect the extension cables, peripheral device cables, input/output

cables and battery connecting cable securely to their designated connectors. Loose connections may cause malfunctions.

Turn off the power to the PLC before attaching or detaching the following devices. Failure to do so may cause equipment failures or malfunctions. - Peripheral devices, expansion adapter, and connector conversion adapter - Extension modules, bus conversion module, connector conversion

module, and battery

Item Specification

Operating ambient

temperature*1 -20 to 55 (-4 to 131), non-freezing*2

Storage ambient temperature

-25 to 75 (-13 to 167), non-freezing

Operating ambient humidity 5 to 95%RH, non-condensing*3

Storage ambient humidity

5 to 95%RH, non-condensing

Vibration

resistance*4*5

Frequency (Hz)

Acceleration (m/s2)

Half amplitude (mm)

Sweep count

Installed on DIN

rail

5 to 8.4 1.75 10 times each in X, Y, Z directions (80 min in each direction)

8.4 to 150 4.9

Shock

resistance*4 147 m/s2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z

Noise durability By noise simulator of 1000 Vp-p noise voltage, 1 s noise width and 30 to 100 Hz noise frequency

Dielectric withstand voltage*6 500 V AC for 1 minute Between batch of all

terminals and ground terminalInsulation

resistance*6 10 M or higher by 500 V DC insulation resistance tester

Grounding Class D grounding (Grounding resistance: 100 or less)

*7

Working atmosphere

Free from corrosive or flammable gas and excessive conductive dusts

Operating

altitude*8 0 to 2000 m

Installation location Inside a control panel*9

Overvoltage

category*10 II or less

Pollution

degree*11 2 or less

Page 35

*1 The simultaneous ON ratio of available PLC inputs or outputs changes with respect to the ambient temperature. In the case where operating ambient temperature is lower than 0, the specifications are different from the above description. Refer to MELSEC iQ-F FX5UC User's Manual (Hardware).

*2 The operating ambient temperature is 0 to 55 (32 to 131) for products manufactured before June 2016. For intelligent function modules, refer to the manual for each product.

*3 When used in a low-temperature environment, use in an environment with no sudden temperature changes. If there are sudden temperature changes because of opening/closing of the control panel or other reasons, condensation may occur, which may cause a fire, fault, or malfunction. Furthermore, use an air conditioner in dehumidifier mode to prevent condensation.

*4 The criterion is shown in IEC61131-2. *5 When the system has equipment which specification values are lower

than above mentioned vibration resistance specification values, the vibration resistance specification of the whole system is corresponding to the lower specification.

*6 For dielectric withstand voltage test and insulation resistance test of each product, refer to the following manual.

Refer to MELSEC iQ-F FX5UC User's Manual (Hardware). *7 For grounding, refer to Section 3.2. *8 The PLC cannot be used at a pressure higher than the atmospheric

pressure to avoid damage. *9 The programmable controller is assumed to be installed in an environment

equivalent to indoor. *10 This indicates the section of the power supply to which the equipment is

assumed to be connected between the public electrical power distribution network and the machinery within premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.

*11 This index indicates the degree to which conductive material is generated in the environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. Temporary conductivity caused by condensation must be expected occasionally.

2.2 Installation location Install the PLC in an environment conforming to the generic specifications (Section 2.1), installation precautions. Installation location in enclosure

Space in enclosure Extension devices can be connected on the left and right sides of the CPU module. If you intend to add extension devices in the future, keep necessary spaces on the left and right sides.

2.3 Procedures for installing to and detaching from DIN rail The products can be installed on a DIN46277 rail [35 mm wide]. This section explains the installations of the CPU modules. 2.3.1 Installation

1) Push out all DIN rail mounting hooks (below fig. A)

F X

5- C

32 E

X

FX 5-

23 2A

D P

FX 5-

C 16

E Y

R /D

-T S

A

A

50 mmA

A

A FX5UC

CPU module

1 A A

1

Page 37

2) Fit the upper edge of the DIN rail mounting groove (right fig. B) onto the DIN rail.

3) Lock the DIN rail mounting hooks (below fig. C) while pressing the PLC against the DIN rail.

2.4 Connection of power supply connector Use the power connector to supply power to the CPU module. For details, refer to MELSEC iQ-F FX5UC User's Manual (Hardware).

2.5 Connection to input/output connector The input/output connectors of the CPU modules (Connector type) conform to MIL-C-83503. For details, refer to MELSEC iQ-F FX5UC User's Manual (Hardware). 1) Compliant connectors (commercially available connectors)

Use a 20-pin (1-key) socket connector conforming to MIL-C-83503. Confirm in advance that the connectors do not interfere with other parts including connector covers.

2) Input/output cables (available from Mitsubishi) Input/output cables with attached connectors are available.

3) Connectors for user-made input/output cables (available from Mitsubishi) Users should provide electric wires and a pressure bonding tool.

4) Certified connectors (commercially available connectors) Connectors made by DDK Ltd. shown in item 3).

Model names Length Description Shape

FX-16E-500CAB-S 5 m General-purpose input/output cable

Single wire (Wire color: red)

PLC side: A 20-pin connector

FX-16E-150CAB 1.5 m Cables for connecting the terminal module with input/output connectors. For terminal module connection, refer to MELSEC iQ-F FX5UC User's Manual (Hardware).

Flat cables (with tube)

A 20-pin connector at both ends

FX-16E-300CAB 3 m

FX-16E-500CAB 5 m

FX-16E-150CAB-R 1.5 m Round multicore

cables

A 20-pin connector at both ends

FX-16E-300CAB-R 3 m

FX-16E-500CAB-R 5 m

Model name and composition of input/output connector

Applicable electric wire (UL-1061 are recommended) and tool

Our model name Details of part

(made by DDK Ltd.) Electric wire

size Pressure bonding tool

(made by DDK Ltd.)

FX2C-I/O- CON for flat cable

10- piece set

Solderless connector FRC2-A020-30S

AWG28

(0.1 mm2) 1.27 pitch, 20-core

357J-4674D: Main body 357J-4664N: Attachment

FX2C-I/O- CON-S for bulk wire

5- piece set

Housing HU-200S2-001 Solderless contact HU-411S

AWG22

(0.3 mm2) 357J-5538

FX2C-I/O- CON-SA for bulk wire

5- piece set

Housing HU-200S2-001 Solderless contact HU-411SA

AWG20

(0.5 mm2) 357J-13963

B

C 3

Page 56

2.6 Connection to input/output terminal block The input/output terminal blocks of the products which have -TS at the end of their model name conform to spring clamp terminal block. For details, refer to MELSEC iQ-F FX5UC Users Manual (Hardware). 1) Wire size

2) Treatment of wire ends When not using a ferrule, strip the cable about 10 mm from the tip and connect it as a strand wire so that the wires do not separate. When using a ferrule, strip the cable about 10 mm from the tip to connect a wire ferrule at the striped area. Failure to do so may result in electric shock or short circuit between adjacent terminals because the conductive part. If the wire strip length is too short, it may result in the poor contact to the spring clamp terminal part. When using a wire ferrule with an insulating sleeve, choose a wire with proper cable sheath referring to the above outside dimensions, otherwise the wire cannot be inserted easily.

The following table shows wire ferrules and tools for wire ferrules compatible with the terminal block. Use of items other than these may result in not being able to remove the wire ferrule, so carefully check that the wire ferrule can be unplugged.

3) Connection and disconnection of the cable Spring clamp terminal block is the push-in type, therefore, wiring without a tool is possible only by inserting the connecting terminal to the terminal block. However, the stranded wire does not comply with the push-in type, and a tool is required for connecting cables. Connection of the cable

Fully insert a cable or bar solderless terminal whose end has been properly processed into the wire insertion opening. If the cable or bar solderless terminal cannot be inserted with this procedure, fully insert the cable or bar solderless terminal while pushing the open/close button with a flathead screwdriver having a tip width of 2.0 to 2.5 mm. After fully inserting the cable, remove the screwdriver.

Do not tighten terminal screws exceeding the specified torque range. Otherwise it may cause equipment failure or malfunction. When wiring with the thick electric wire, make sure to prevent the conductive parts from protruding to the front of the terminal block.

Disconnection of the cable While pushing the open/close button with a flathead screwdriver having a tip width of 2.0 to 2.5 mm, disconnect the cable or bar solderless terminal.

2.7 Connection to built-in RS-485 Communication terminal block

The built-in RS-485 Communication terminal block conform to terminal block (European type). For details, refer to MELSEC iQ-F FX5UC Users Manual (Hardware). 1) Wire size

No. of wire per terminal

Wire size

Single wire/Strand wire

Ferrules with insulation sleeve

Ferrules without insulation sleeve

One wire AWG24 to 16 AWG23 to 19 AWG23 to 16

Manufacturer Model Wire size Crimp tool

PHOENIX CONTACT GmbH & Co. KG

AI 0.5-10 WH 0.5 mm2

CRIMPFOX 6 AI 0.75-10 GY 0.75 mm2

A 1.0-10 1.0 mm2

A 1.5-10 1.5 mm2

Manufacturer Model

PHOENIX CONTACT GmbH & Co. KG SZS 0.42.5 VDE

No. of wire per terminal

Wire size

Solid wire/Stranded wire

Ferrules with insulating sleeve

1 AWG22 to 20 AWG22 to 20

2 AWG22

10 mm

Contact area (Crimp area)

16 to 18 mm2 to 2.8 mm

Insulation sleeve - Ferrule with insulation sleeve

10 mm

- Strand wire/single wire

Page 58

2) Treatment of wire ends Strip the coating of strand wire and twist the cable core before connecting it, or strip the coating of single wire before connecting it. An alternative connection is to use a ferrule with insulating sleeve.

When using a wire ferrule with an insulating sleeve, choose a wire with proper cable sheath referring to the above outside dimensions, otherwise the wire cannot be inserted easily. Tighten the screws to a torque of 0.22 to 0.25 Nm. Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do so may cause equipment failures or malfunctions.

3) Tool For tightening the terminal, use a commercial ly avai lable smal l screwdriver having a straight form that is not widened toward the end as shown right. Note: If the diameter of screwdriver grip is too small, tightening torque may not be achieved. To achieve the appropriate tightening torque shown in the table above, use the following screwdriver or appropriate replacement (grip diameter: approximately 25 mm).

3. Specifications and examples of external wiring

As for the details of the power supply wiring and input/output wiring, refer to MELSEC iQ-F FX5UC User's Manual (Hardware)..

Manufacturer Model Caulking tool

PHOENIX CONTACT GmbH & Co. KG AI 0.5-6WH CRIMPFOX 6

Manufacturer Model names

PHOENIX CONTACT GmbH & Co. KG SZS 0.4 2.5

DESIGN PRECAUTIONS

Make sure to set up the following safety circuits outside the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. - Most importantly, set up the following: an emergency stop circuit, a

protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits).

- Note that when the CPU module detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the CPU module occurs in an input/ output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.

- Note that when an error occurs in a relay, transistor or triac of an output circuit, the output might stay on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.

Construct an interlock circuit in the program so that the whole system always operates on the safe side before executing the control (for data change) of the PLC in operation. Read the manual thoroughly and ensure complete safety before executing other controls (for program change, parameter change, forcible output and operation status change) of the PLC in operation. Otherwise, the machine may be damaged and accidents may occur due to erroneous operations.

WIRING PRECAUTIONS

Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product.

Make sure to attach the terminal cover, provided as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.

The rating temperature of the cable should be 80 or more.

9 mm

- Strand wire/single wire

8 mm

14 mm2.6 mm

Insulating sleeve Contact area (Crimp area)

- Ferrule with insulation sleeve

0.4 mm 2.5 mm

With straight tip

Page 60

3.1 Power supply specifications and external wiring 3.1.1 Power supply specifications [CPU module]

*1 This item shows value when only the CPU module is used. The value in [ ] is the value in the maximum configuration connectable to the CPU module. (The value does not include the external 24 V DC power supply of extension devices)

WIRING PRECAUTIONS

Please separate the AC power supply from the AC commercial power supply network with an insulation transformer when connecting to AC input module or AC output module.

Make sure to properly wire to the terminal block (European type) in accordance with the following precautions. Failure to do so may cause electric shock, equipment failures, a short- circuit, wire breakage, malfunctions, or damage to the product. - The disposal size of the cable end should follow the dimensions

described in the manual. - Tightening torque should follow the specifications in the manual. - Twist the ends of stranded wires and make sure that there are no loose wires. - Do not solder-plate the electric wire ends. - Do not connect more than the specified number of wires or electric

wires of unspecified size. - Affix the electric wires so that neither the terminal block nor the

connected parts are directly stressed. Make sure to properly wire to the spring clamp terminal block in

accordance with the following precautions. Failure to do so may cause electric shock, equipment failures, a short- circuit, wire breakage, malfunctions, or damage to the product. - The disposal size of the cable end should follow the dimensions

described in the manual. - Twist the ends of stranded wires and make sure that there are no loose wires. - Do not solder-plate the electric wire ends. - Do not connect more than the specified number of wires or electric

wires of unspecified size. - Affix the electric wires so that neither the terminal block nor the

connected parts are directly stressed.

WIRING PRECAUTIONS

Perform class D grounding (grounding resistance: 100 or less) of the grounding

terminal on the CPU module and extension modules with a wire 2 mm2 or thicker. Do not use common grounding with heavy electrical systems (refer to section 3.3).

When drilling screw holes or wiring, make sure that cutting or wiring debris do not enter the ventilation slits of the PLC. Failure to do so may cause fire, equipment failures or malfunctions.

Connect the power supply wiring to the dedicated terminals described in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out.

Do not wire vacant terminals externally. Doing so may damage the product. Make sure to observe the following precautions in order to prevent any

damage to the machinery or accidents due to malfunction of the PLC caused by abnormal data written to the PLC due to the effects of noise. - Do not bundle the power line, control line and communication cables

together with or lay them close to the main circuit, high-voltage line, load line or power line. As a guideline, lay the power line, control line and communication cables at least 100 mm away from the main circuit, high-voltage line, load line or power line.

- Ground the shield of the shielded wire or shielded cable at one point on the PLC. However, do not use common grounding with heavy electrical systems.

Item Specification

Power supply voltage 24 V DC

Voltage fluctuation range +20%, -15%

Allowable instantaneous power failure time

Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less.

Power fuse 125 V 3.15 A Time-lag Fuse

Rush current

FX5UC-32M/ 35 A max. 0.5 ms or less/24 V DC

FX5UC-64MT/ FX5UC-96MT/ 40 A max. 0.5 ms or less/24 V DC

Power consumption *1

FX5UC-32M/ 5 W/24 V DC [30 W/24 V DC +20%, -15%]

FX5UC-64MT/ 8 W/24 V DC [33 W/24 V DC +20%, -15%]

FX5UC-96MT/ 11 W/24 V DC [36 W/24 V DC +20%, -15%]

24 V DC built-in power supply capacity 500 mA

5 V DC built-in power supply capacity 720 mA

Page 62

3.1.2 Example of external wiring 24 V DC power is supplied to the CPU module. CPU module supplies power through dedicated power connector. For the details, refer to the MELSEC iQ-F FX5UC User's Manual (Hardware).

*1 Class D grounding See section 3.3 for details.

3.2 Grounding Ground the PLC as stated below. Perform class D grounding. (Grounding resistance: 100 or less) Ground the PLC independently if possible.

If it cannot be grounded independently, ground it jointly as shown below.

Bring the grounding point close to the PLC as much as possible so that the ground cable can be shortened.

3.3 Input specifications and external wiring 3.3.1 Input specifications [24 V DC input type]

Item Specification

Input signal voltage 24 V DC +20%, -15%

Input impedance

CPU module

X0 to X17 4.3 k

X20 and subsequent 5.6 k

I/O module 5.6 k

Input signal current

CPU module

X0 to X17 5.3 mA/24 V DC

X20 and subsequent

4.0 mA/24 V DC

I/O module 4.0 mA/24 V DC

ON input sensitivity current

CPU module

X0 to X17 3.5 mA or more

X20 and subsequent

3.0 mA or more

I/O module 3.0 mA or more

OFF input sensitivity current 1.5 mA or less

Input response time Refer to MELSEC iQ-F FX5UC User's Manual (Hardware)

Input signal form (Input sensor form)

FX5UC-MT/D FX5-CEX/D FX5-C32ET/D

No-voltage contact input NPN open collector transistor

FX5UC-MT/DSS FX5UC-32M/-TS FX5-CEX/DS FX5-C32EX/DS-TS FX5-C32ET/DSS FX5-C32ET/DS(S)-TS

Sink input: - No-voltage contact input - NPN open collector transistor

Source input: - No-voltage contact input - PNP open collector transistor

Input operation display LED on panel turns on when input. (DISP switch IN side.)

24 V DC

Breaker, Circuit protector, Fuse etc. Power

on

Emergency stop

Power supply for loads connected to CPU module output terminals

MC

PL

CPU module

Fuse

*1

PLC Other equipment PLC Other

equipment PLC Other equipment

Shared grounding (Good condition)

Common grounding (Not allowed)

Independent grounding (Best condition)

Page 81

3.3.2 Examples of input wiring 1. Examples of input wiring (FX5UC-MT/D)

2. Examples of input wiring (FX5UC-MT/DSS, FX5UC-32M/-TS)

3.4 Transistor output specifications and external wiring 3.4.1 Transistor output specifications

Item Specification

Output form

FX5UC-MT/D, FX5UC-32MT/DS-TS, FX5-CEYT/D, FX5-C32EYT/D-TS, FX5-C32ET/D, FX5-C32ET/DS-TS,

Transistor (Sink)

FX5UC-MT/DSS, FX5UC-32MT/DSS-TS, FX5-CEYT/DSS, FX5-C32EYT/DSS-TS, FX5-C32ET/DSS(-TS)

Transistor (Source)

External power supply 5 to 30 V DC

Max. load

CPU module

Y0 to Y3 0.3 A/point Make sure that the total load current of 8 load points is 0.8 A*1 or less.

Y4 and subsequent 0.1 A/point

I/O module 0.1 A/point

Open circuit leakage current 0.1 mA or less/30 V DC

COM

X0

X1

X2

COM

COM

X0

COM

-

+

-

+

24 V DC Fuse

*1

Breaker, Circuit protector, Fuse, etc.

Three wire sensor NPN

[1]: FX5UC-MT/D [2]: FX5-CEX/D, FX5-C32ET/D

[1]

[2]

*1 Class D grounding See section 3.3 for details.

COM0

X0

X1

X2

COM0

COM0

X0

COM0

-

+

COM0

X0

X1

X2

COM0

COM0

X0

COM0

-

+

[1]: FX5UC-MT/DSS, FX5UC-32M/-TS [2]: FX5-CEX/DS, FX5-C32EX/DS-TS, FX5-C32ET/DSS, FX5-C32ET/DS(S)-TS

*1 Class D grounding See section 3.3 for details. *2 For -TS type, the "COM0" terminal is the "S/S" terminal.

1) Sink input

[1]

[2]

[1]

[2]

Fuse

*1 *2

*2

*2

*2

*2

*2

*2

*2

Breaker, Circuit protector, Fuse, etc.

Three wire sensor NPN

24 V DC 24 V DC Fuse

*1

2) Source input Breaker, Circuit protector, Fuse, etc.

Three wire sensor PNP

Page 83

*1 When two COM (or +V) terminals are connected outside the CPU module, resistance load is 1.6 A or less. Where indicates: 0, 1, or 2 As for the number of outputs per common terminal, refer to the following manual.

Refer to MELSEC iQ-F FX5UC User's Manual (Hardware). 3.4.2 External wiring of transistor output 1. External wiring of sink output type

2. External wiring of source output type

3.5 Relay output specifications and external wiring 3.5.1 Relay output specifications

*1 When two COM terminals are connected outside the CPU module, resistance load is 8 A or less. Where indicates: 0 or 1

3.5.2 External wiring of relay output 1. External wiring of DC power supply

ON voltage

CPU module

Y0 to Y3 1.0 V or less

Y4 and subsequent

1.5 V or less

I/O module 1.5 V or less

Respon se time

OFF ON

CPU module

Y0 to Y3 2.5 s or less/10 mA or more (5 to 24 V DC)

Y4 and subsequent

0.2 ms or less/100 mA (at 24 V DC)

I/O module 0.2 ms or less/100 mA (at 24 V DC)

Output operation display LED on panel turns on when output. (DISP switch OUT side.)

Item Specification

External power supply 30 V DC or less 240 V AC or less ("250 V AC or less" if not a CE, UL, cUL compliant item)

Max. load 2 A/point Make sure that the total load current of 8 load points is 4 A*1 or less.

Min. load 5 V DC, 2 mA (reference value)

Open circuit leakage current

Response time OFFON Approx. 10 ms

Output operation display LED on panel turns on when output.

Item Specification

COM0 COM0 Y0 Y1 Y2

24 V DC

LoadLoadLoad

Fuse

Emergency stop

FX5UC-MT/D FX5UC-32MT/DS-TS FX5-CEYT/D FX5-C32EYT/D-TS FX5-C32ET/D FX5-C32ET/DS-TS

+V0 +V0 Y0 Y1 Y2

24 V DC

LoadLoadLoad

Fuse

Emergency stop

FX5UC-MT/DSS FX5UC-32MT/DSS-TS FX5-CEYT/DSS FX5-C32EYT/DSS-TS FX5-C32ET/DSS(-TS)

COM0 Y0 Y1 Y2

24 V DC

LoadLoadLoad Fuse

Emergency stop

FX5UC-32MR/DS-TS FX5-C16EYR/D-TS

COM0

Page 85

2. External wiring of AC power supply

3.6 Built-in Ethernet communication specifications and external wiring

As for the details on the built-in Ethernet communication specifications and external wiring, refer to the following manual.

Refer to MELSEC iQ-F FX5 User's Manual (Ethernet Communication).

3.6.1 Communication specification

*1 IEEE802.3x flow control is not supported. *2 The value indicates the number of connectable stages when a repeater

hub is used. Contact the manufacturer of the switching hub for the number of connectable stages when using a switching hub.

*3 The first device for MELSOFT connection is not included in the number of connections. (The second and the following devices are included.)

*4 The CC-Link IE field network Basic, FTP server, SNTP client, Web server and simple CPU communication function are not included in the number of connections.

*5 If the first octet is 0 or 127, a parameter error (2222H) will occur. (Example: 0.0.0.0, 127.0.0.0, etc.)

3.6.2 Wiring For the wiring, refer to the following manual.

Refer to MELSEC iQ-F FX5 User's Manual (Ethernet Communication).

3.6.3 Pin Configuration The connector of the built-in Ethernet communication are arranged as follows:

Item Specification

Data transmission speed 100/10 Mbps

Communication mode Full-duplex (FDX)/Half-duplex (HDX)*1

Interface RJ45 connector

Transmission method Base band

Maximum segment length (The distance between hub and node) 100 m

Cascade connection

100BASE-TX Max. 2 stages*2

10BASE-T Max. 4 stages*2

Protocol type

CC-Link IE field network Basic, MELSOFT connection, SLMP (3E frame), Socket communication, Predefined protocol support, FTP Server, MODBUS/TCP communication, SNTP client, Web server (HTTP), Simple CPU communication function

Number of simultaneously open connections allowed

Total of 8 connections*3*4

(Up to 8 external devices can access one CPU module at the same time.)

Hub*1 Hubs with 100BASE-TX or 10BASE-T ports can be used.

Insulation method Pulse transformer

IP address*5 Initial value: 192.168.3.250

Pin No. Signal Contents

1 TXD+ Transmit data (+)

2 TXD- Transmit data (-)

3 RXD+ Receive data (+)

4 Not used -

5 Not used -

6 RXD- Receive data (-)

7 Not used -

8 Not used -

COM0 Y0 Y1 Y2

100 V AC

LoadLoadLoad

Fuse

Emergency stop

FX5UC-32MR/DS-TS FX5-C16EYR/D-TS

COM0

8

1

Page 87

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubish

Mitsubishi Electric FX5UC User Manual | Manualsnet (2024)
Top Articles
Fototour verlassener Fliegerhorst Schönwald [Lost Place Brandenburg]
Ati Learning Template
Nybe Business Id
Dannys U Pull - Self-Service Automotive Recycling
Hotels
Wordscapes Level 5130 Answers
Urinevlekken verwijderen: De meest effectieve methoden - Puurlv
Dark Souls 2 Soft Cap
Best Cav Commanders Rok
Craigslist Chautauqua Ny
Chastity Brainwash
Hallelu-JaH - Psalm 119 - inleiding
Cooktopcove Com
2015 Honda Fit EX-L for sale - Seattle, WA - craigslist
Games Like Mythic Manor
Minecraft Jar Google Drive
Blackwolf Run Pro Shop
Tygodnik Polityka - Polityka.pl
Bing Chilling Words Romanized
Delaware Skip The Games
Is The Yankees Game Postponed Tonight
Glover Park Community Garden
Cookie Clicker Advanced Method Unblocked
Weldmotor Vehicle.com
Skymovieshd.ib
Pacman Video Guatemala
How do you get noble pursuit?
Ordensfrau: Der Tod ist die Geburt in ein Leben bei Gott
Log in or sign up to view
Osrs Important Letter
Sinai Sdn 2023
Otis Offender Michigan
Grandstand 13 Fenway
Rocksteady Steakhouse Menu
Trebuchet Gizmo Answer Key
Colorado Parks And Wildlife Reissue List
Retire Early Wsbtv.com Free Book
State Legislatures Icivics Answer Key
Has any non-Muslim here who read the Quran and unironically ENJOYED it?
Gvod 6014
Join MileSplit to get access to the latest news, films, and events!
11526 Lake Ave Cleveland Oh 44102
Dwc Qme Database
QVC hosts Carolyn Gracie, Dan Hughes among 400 laid off by network's parent company
How Big Is 776 000 Acres On A Map
Nimbleaf Evolution
Mcoc Black Panther
All Buttons In Blox Fruits
Aaca Not Mine
ESPN's New Standalone Streaming Service Will Be Available Through Disney+ In 2025
Zalog Forum
Morgan State University Receives $20.9 Million NIH/NIMHD Grant to Expand Groundbreaking Research on Urban Health Disparities
Latest Posts
Article information

Author: Mr. See Jast

Last Updated:

Views: 5986

Rating: 4.4 / 5 (75 voted)

Reviews: 82% of readers found this page helpful

Author information

Name: Mr. See Jast

Birthday: 1999-07-30

Address: 8409 Megan Mountain, New Mathew, MT 44997-8193

Phone: +5023589614038

Job: Chief Executive

Hobby: Leather crafting, Flag Football, Candle making, Flying, Poi, Gunsmithing, Swimming

Introduction: My name is Mr. See Jast, I am a open, jolly, gorgeous, courageous, inexpensive, friendly, homely person who loves writing and wants to share my knowledge and understanding with you.